AS 61869.13:2021 pdf free download - lnstrument transformers Part 13: Stand-alone merging unit

AS 61869.13:2021 pdf free download – lnstrument transformers Part 13: Stand-alone merging unit

Posted by

AS 61869.13:2021 pdf free download – lnstrument transformers Part 13: Stand-alone merging unit.
This part of IEC 61869 is a product standard and covers only additional requirements for standalone merging units (SAMU5) used for AC applications having rated frequencies from 15 Hz to 100 Hz. The digital output format specification is not covered by this document: it Is standardized In IEC 61869-9 as an application of IEC 61850. which specifies the power utility communication architecture.
This document covers SAMUS having standardized analogue inputs (for example: 1 A. 5 A, 3,25 V 1 ‘3 or 100 V I ,3) provided by instrument transformers compliant with relevant product standards (e.g. IEC 61869-2 to IEC 61869-5, IEC 61869-7, IEC 61869-8. IEC 61869-10. 1EC61869-11, IEC 60044-1 to 1EC60044-6, IEC 60185, IEC 60186, IEEE C57.13), and alms to convert them to the digital output compliant with IEC 61869-9. Other input and output types are outside the scope of this document. Appropriate SAMU functionality can be combined with swltchgear controller functionality defined in IEC 62271.3 or other lED functionality defined in IEC 60255 (all parts).
Cyber security requirements are outside the scope of this document and are covered by the IEC 62351 series.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Clause 2 of IEC 61869-1:2007 is applicable with the following additions:
IEC 60068-2-1:2007, Environmental testing — Part 2-1: Tests — Test A: Cold
IEC 60068-2-2:2007, Environmental testing — Part 2-2: Tests — Test B: Dry heat
IEC 60068-2-14:2009. Environmental testing — Part 2-14: Tests — Test N: Change of temperature
IEC 60068-2-30:2005. Environmental testing – Part 2-30.’ Tests — Test Db. Damp heat, cyclic (12 • 12 h cycle)
IEC 60068-2-78:2012, Environmental testing — Part 2-78: Tests — Test Cab: Damp heat, steady state
IEC 60255-27:2013, Measuring relays and protection equipment — Part 27: Product safety requirements
IEC 60664-1:2020, Insulation coordination for equipment within low-voltage supply systems — Part 1: Principles, requirements end tests
6.11.3.608 Electrical fast transient/burst
Subclause 6.11.3.608 of IEC 618694:2016 is applicable with the following additions:
The tesi level for SAMU shielded input ports designed to meet the protection by equipotential bonding (PEB) requirements with workrng voltage lower than or equal to 150 V and communication ports shall be Level 2.
6.11.3.609 Oscillatory wave immunity
Subclause 6.11.3.609 of IEC 61869-6:2016 is applicable with the following additions:
The test shall be performed at 1 MHz.
The test level for SAMU shielded input ports designed to meet the PEB requirements with working voltage lower than or equal to 150 V and communication ports shall be Level 2 and restricted to common mode only.
6.11.3.1301 Voltage ripple on DC power supply
The purpose of this test is to verify the SAMU immunity to voltage ripple disturbance on DC power supply defined in IEC 61000-4-17:1999.
6.11.3.1302 Gradual shutdown and start-up test
The purpose of this test is to verify the SAMU immunity to slow DC power supply disturbances affecting the device shut-down and start-up behaviour.
6.11.4 RequIrement for transmItted ov.rvoltages
Subclause 6,11.4 of IEC 61869-1:2007 ês not applicable to SAMLJ,
6.11.601 EmissIon requirements
Subclause 6. .601 of IEC 61869-6;2016 is replaced w.ih the following.
SAMU shall comply with limits given in CISPR 11 Group 1 — class A for radiated emission below 1 GHz and with limits in CISPR 32:2015/AMDI:2019. Table A.3 class A for radiated emission above 1 GHz and shall be tested accordingly.