ASME A112.19.13:2002 pdf download.ELECTROHYDRAULIC WATER CLOSETS.
ASME A112.19.13 establishes performance. electricalielectronic conformance, temperature, life cyclc. marking. and identification requirements for cleclrohydraulic waler closets,
The use of alternate materials or methJs arc permitted, provided the proposed material or method complies with the perftrmance requirements and intent of this Standard.
1.2 Units of Measurement
Values are stated in U.S. Customary units and the International System of Units (Sb. The U.S. Customary units shall be considered as the standard.
1.3 Reference Standards
The following documents form a part of this Standard to the extent specified herein. Unless otherwise indicated. the latest issue shall apply.
ANSI Zl24.4. Plastic Water Closet Bowls and Tanks
Publisher: international Association of Plumbing and Mechanical Officials. 2(X)Ol East Walnut Drive South, Walnut. CA 91789
ASME Al l2.19.2M.Vitreous China Plumbing Fixtures ASME Al 12.19.6. Hydraulic Performance Requirements for Water Closets and Urinals
Publisher: The American Society of Mechanical Engineers. ASME Order Department. 22 Law Drive, Box 2300. Fairfield, NJ 07007
UL 62. Flexible Cord and Fixture Wire
UL 157, Gaskets and Seals
UL 244A-1994, Solid-State Controls for Appliances
UL 746C, Polymeric Materials — Used in Electrical Equipment Evaluations
UL 778, Motor Operated Water Pumps
Lii. 796. Printed-Wiring Boards
UI. 817, Cord Sets and Power-Supply Cords
UL 1585, Class 2 and Class 3 Transformers
Publisher: Underwriters Laboratories Inc., 333 Ptingsten Road, Norihbrook, IL 60062
2.9 Pump Temperature Testing
The pump shall be tested as described in para. 2.2(b), section 34 of UL 778. at the maximum duty cycle the pump will allow.
2.10 Wiring Harness Entrance and Location
The wiring harness and electrical controls not en closed in the pump housing shall be located above the flood level rim of the tank or reservoir and above the drains or overflows.
2.11 Life Cycle Test
The electrical components and pump shall pass a 75,000 life cycle test. The test shall be performed on the waler closet at the maximum cycle rate the electronic controls will allow. Upon completion of the life cycle test, the average volume per (lush shall not vary more than 0.15 gal (0.57 L) or 10%, whichever is greater.
3 MARKING AND INSTRUCTION MANUAL
3.1 Marking
3.1.1 Water Closet. The water closet shall he legibly marked as specitied in ASME A1l2.l9.2M and other standards referenced in this Standard (see para. 1.3).
3.1.2 Pump. The pump shall have the following markings visible on it in its normal operating position and a second label visible on the exterior of the water closet or cord stating:
WARNING:
To reduce the hsk of shock. connect only to a properl groudcd l’,pc receptacle, protected b a roundJault circuit interrupter (;FCIt.
The word warnim’ shall be a minimum of /32 in. (2.4 mm) high.
3.2 Instruction Manual
An instruction manual shall be provided that includes instructions for routine maintenance and operation.